------------------------------------------------------------------------------- -- -- CONTEG-DATABUS-MIB.txt: Conteg MIB for databus devices -- ------------------------------------------------------------------------------- CONTEG-DATABUS-MIB DEFINITIONS ::= BEGIN IMPORTS MODULE-IDENTITY, OBJECT-TYPE, Integer32, Unsigned32, NOTIFICATION-TYPE FROM SNMPv2-SMI OBJECT-GROUP, NOTIFICATION-GROUP, MODULE-COMPLIANCE FROM SNMPv2-CONF TEXTUAL-CONVENTION, DisplayString FROM SNMPv2-TC contegMgmt FROM CONTEG-SMI; contegDatabusMIB MODULE-IDENTITY LAST-UPDATED "202302070000Z" -- February 7th, 2023 ORGANIZATION "" CONTACT-INFO "" DESCRIPTION "This MIB describes the SNMP functions of network enabled databus devices. " REVISION "202302070000Z" -- February 7th, 2023 DESCRIPTION "1. Added sdbDevStOutletUnlockOverride 2. Added sdbDevCfTempSensors 3. Added sdbDevCfTotals 4. Added sdbDevTotalsResidualMaxAmps" REVISION "202106160000Z" -- June 16th, 2021 DESCRIPTION "1. Added performance monitoring registers 2. Added sdbDevStUsbMode register 3. Added sdbDevIdDeviceType register" REVISION "202009170000Z" -- September 17th, 2020 DESCRIPTION "1. Added sdbDevCfBranches register 2. Added sdbDevBranchTable with registers for table entries 3. Added sdbDevTotals with registers for table entries" ::= { contegMgmt 1 } CentiValue ::= TEXTUAL-CONVENTION DISPLAY-HINT "d-2" STATUS current DESCRIPTION "Data type for reporting generic measurements associated with environmental sensors. If the underlying hardware sensor indicates 21.1 degrees Celsius, then the SNMP agent will report a value of 2110 CentiValue." SYNTAX Integer32 (0..327680) KiloWattHour ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "Data type for reporting measurements associated with energy accumulation sensors. If the underlying hardware sensor indicates 1 kWh, then the SNMP agent will report a value of 1 kWh." SYNTAX Integer32 (0..16777215) -- START MIB -- CentiAmpere ::= TEXTUAL-CONVENTION DISPLAY-HINT "d-2" STATUS current DESCRIPTION "Data type for reporting measurements and thresholds associated with current sensors. If the underlying hardware sensor indicates 1.1 A, then the SNMP agent will report a value of 110 CentiAmpere." SYNTAX Integer32 (0..327680) CentiCelsius ::= TEXTUAL-CONVENTION DISPLAY-HINT "d-2" STATUS current DESCRIPTION "Data type for reporting sensor readings associated with temperature sensors. If the underlying hardware sensor indicates 20.1 degrees Celsius, then the SNMP agent will report a value of 2010 CentiCelsius." SYNTAX Integer32 (0..9900) CentiPercent ::= TEXTUAL-CONVENTION DISPLAY-HINT "d-2" STATUS current DESCRIPTION "Data type for reporting calculated percentages. If the calculated percentage is 98.3%, then the SNMP agent will report a value of 9830 CentiPercent." SYNTAX Integer32 (0..10000) CentiVolt ::= TEXTUAL-CONVENTION DISPLAY-HINT "d-2" STATUS current DESCRIPTION "Data type for reporting measurements and thresholds associated with voltage sensors. If the underlying hardware sensor indicates 231.1 V, then the SNMP agent will report a value of 23110 CentiVolt." SYNTAX Integer32 (0..327680) MilliSecond ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "Duration in milliseconds" SYNTAX Integer32 Second ::= TEXTUAL-CONVENTION DISPLAY-HINT "d" STATUS current DESCRIPTION "Duration in seconds." SYNTAX Integer32 sdbMIBNotifications OBJECT IDENTIFIER ::= { contegDatabusMIB 0 } sdbMIBObjects OBJECT IDENTIFIER ::= { contegDatabusMIB 1 } sdbMIBConformance OBJECT IDENTIFIER ::= { contegDatabusMIB 2 } sdbMgmt OBJECT IDENTIFIER ::= { sdbMIBObjects 1} sdbDevice OBJECT IDENTIFIER ::= { sdbMIBObjects 2 } sdbMgmtStatus OBJECT IDENTIFIER ::= { sdbMgmt 1 } sdbMgmtControl OBJECT IDENTIFIER ::= { sdbMgmt 2 } sdbDevIdentification OBJECT IDENTIFIER ::= { sdbDevice 1 } sdbDevConfiguration OBJECT IDENTIFIER ::= { sdbDevice 2 } sdbDevSystemStatus OBJECT IDENTIFIER ::= { sdbDevice 3 } sdbDevReset OBJECT IDENTIFIER ::= { sdbDevice 4 } sdbDevSettings OBJECT IDENTIFIER ::= { sdbDevice 5 } sdbDevInput OBJECT IDENTIFIER ::= { sdbDevice 6 } sdbDevOutlet OBJECT IDENTIFIER ::= { sdbDevice 7 } sdbDevSensor OBJECT IDENTIFIER ::= { sdbDevice 8 } sdbDevPerformance OBJECT IDENTIFIER ::= { sdbDevice 9 } sdbDevBranches OBJECT IDENTIFIER ::= { sdbDevice 10 } sdbDevTotals OBJECT IDENTIFIER ::= { sdbDevice 11 } sdbMIBCompliances OBJECT IDENTIFIER ::= { sdbMIBConformance 1 } sdbMIBGroups OBJECT IDENTIFIER ::= { sdbMIBConformance 2 } sdbMgmtStsDevices OBJECT-TYPE SYNTAX Integer32 (1..512) MAX-ACCESS read-only STATUS current DESCRIPTION "The number of devices on the databus." ::= { sdbMgmtStatus 1} sdbMgmtStsAddressableDevices OBJECT-TYPE SYNTAX Integer32 (1..255) MAX-ACCESS read-only STATUS current DESCRIPTION "The number of devices on the databus addressable by snmp." ::= { sdbMgmtStatus 2 } sdbMgmtStsNewDevices OBJECT-TYPE SYNTAX Integer32 (1..255) MAX-ACCESS read-only STATUS current DESCRIPTION "The number of new devices on the databus." ::= { sdbMgmtStatus 3 } sdbMgmtStsDuplicateDevices OBJECT-TYPE SYNTAX Integer32 (1..255) MAX-ACCESS read-only STATUS current DESCRIPTION "The number of duplicate devices on the databus." ::= { sdbMgmtStatus 4 } sdbMgmtStsRingState OBJECT-TYPE SYNTAX INTEGER { open(0), closed(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "If the device is in a bridge-like mode, this will indicate the actual state of the databus." ::= { sdbMgmtStatus 5 } sdbMgmtStsRingBreachIndex OBJECT-TYPE SYNTAX Integer32 (0..65535) MAX-ACCESS read-only STATUS current DESCRIPTION "Indicates the breach index if the current state of the data bus is open. If the data bus is closed this has no meaning." ::= { sdbMgmtStatus 6 } sdbMgmtCtrlScan OBJECT-TYPE SYNTAX INTEGER { idle(0), scan(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Perform a bus scan. To verify if scanning is completed the value of this object can be read. During the bus scan the value remains 1. When the bus scan completed the value will be 0." ::= { sdbMgmtControl 1 } sdbMgmtCtrlRenumberAllFromN OBJECT-TYPE SYNTAX Integer32 (0..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "Renumber all devices on the databus. If set to 0 all units will be set to 0. If set to another value, all units will be numbered in sequence starting from the value set." ::= { sdbMgmtControl 2 } sdbMgmtCtrlRenumberZeros OBJECT-TYPE SYNTAX INTEGER { idle(0), renumber(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Renumber all devices on the databus having address 0. Renumbering will be done in sequence. The sequence starts with the highest address found on the databus." ::= { sdbMgmtControl 3 } sdbMgmtCtrlDevicesTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbMgmtCtrlDevicesEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table containing information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsDevices." ::= { sdbMgmtControl 4 } sdbMgmtCtrlDevicesEntry OBJECT-TYPE SYNTAX SdbMgmtCtrlDevicesEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information entry containing objects of a particular databus device." INDEX { sdbMgmtCtrlDevIndex } ::= { sdbMgmtCtrlDevicesTable 1 } SdbMgmtCtrlDevicesEntry ::= SEQUENCE { sdbMgmtCtrlDevIndex Integer32, sdbMgmtCtrlDevUnitAddress Integer32, sdbMgmtCtrlDevHardwareAddress DisplayString, sdbMgmtCtrlDevIsNew Integer32, sdbMgmtCtrlDevIsDuplicate Integer32 } sdbMgmtCtrlDevIndex OBJECT-TYPE SYNTAX Integer32 (1..255) MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique value for each device. Its value ranges between 1 and the value of sdbMgmtStsDevices with a maximum of 255. The value for each device will remain constant until the next scan is performed." ::= { sdbMgmtCtrlDevicesEntry 1 } sdbMgmtCtrlDevUnitAddress OBJECT-TYPE SYNTAX Integer32 (0..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "User defined address. This will be used for addressing the device on the databus." ::= { sdbMgmtCtrlDevicesEntry 2 } sdbMgmtCtrlDevHardwareAddress OBJECT-TYPE SYNTAX DisplayString (SIZE(17)) MAX-ACCESS read-only STATUS current DESCRIPTION "Hardware serial number. This cannot be changed. It can be used as backup unit address. format as 3 unsigned ints separated by dashes: int - int - int" ::= { sdbMgmtCtrlDevicesEntry 3 } sdbMgmtCtrlDevIsNew OBJECT-TYPE SYNTAX INTEGER { no(0), yes(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Indication if the device is new on the databus." ::= { sdbMgmtCtrlDevicesEntry 4 } sdbMgmtCtrlDevIsDuplicate OBJECT-TYPE SYNTAX INTEGER { no(0), yes(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "Indication if the device is conflicting with another device on the databus." ::= { sdbMgmtCtrlDevicesEntry 5 } sdbDevIdTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbDevIdEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table containing identification information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices." ::= { sdbDevIdentification 1 } sdbDevIdEntry OBJECT-TYPE SYNTAX SdbDevIdEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Information entry containing information objects of a particular databus device." INDEX { sdbDevIdIndex } ::= { sdbDevIdTable 1 } SdbDevIdEntry ::= SEQUENCE { sdbDevIdSPDMVersion Integer32, sdbDevIdFirmwareVersion Integer32, sdbDevIdBuildNumber DisplayString, sdbDevIdSalesOrderNumber DisplayString, sdbDevIdProductId DisplayString, sdbDevIdSerialNumber DisplayString, sdbDevIdHardwareAddress DisplayString, sdbDevIdMacAddress DisplayString, sdbDevIdUnitAddress Integer32, sdbDevIdName DisplayString, sdbDevIdLocation DisplayString, sdbDevIdVanityTag DisplayString, sdbDevIdIndex Integer32, sdbDevIdDeviceType Integer32, sdbDevIdLocateUnit Integer32, sdbDevIdConfigType Integer32 } sdbDevIdSPDMVersion OBJECT-TYPE SYNTAX Integer32 (0..9999) MAX-ACCESS read-only STATUS current DESCRIPTION "Data model version." ::= { sdbDevIdEntry 1 } sdbDevIdFirmwareVersion OBJECT-TYPE SYNTAX Integer32 (0..9999) MAX-ACCESS read-only STATUS current DESCRIPTION "The firmware revision number." ::= { sdbDevIdEntry 2 } sdbDevIdBuildNumber OBJECT-TYPE SYNTAX DisplayString (SIZE(0..12)) MAX-ACCESS read-only STATUS current DESCRIPTION "Date and time the firmware was built." ::= { sdbDevIdEntry 3 } sdbDevIdSalesOrderNumber OBJECT-TYPE SYNTAX DisplayString (SIZE(0..16)) MAX-ACCESS read-only STATUS current DESCRIPTION "SP sales order number." ::= { sdbDevIdEntry 4 } sdbDevIdProductId OBJECT-TYPE SYNTAX DisplayString (SIZE(0..16)) MAX-ACCESS read-only STATUS current DESCRIPTION "SP product id." ::= { sdbDevIdEntry 5 } sdbDevIdSerialNumber OBJECT-TYPE SYNTAX DisplayString (SIZE(0..16)) MAX-ACCESS read-only STATUS current DESCRIPTION "SP serial number." ::= { sdbDevIdEntry 6 } sdbDevIdHardwareAddress OBJECT-TYPE SYNTAX DisplayString (SIZE(17)) MAX-ACCESS read-only STATUS current DESCRIPTION "Hardware serial number. This can not be changed. It can be used as backup unit address. Format as 3 unsigned ints separated by dashes (-) e.g. 12345-54321-00000" ::= { sdbDevIdEntry 7 } sdbDevIdMacAddress OBJECT-TYPE SYNTAX DisplayString (SIZE(17)) MAX-ACCESS read-only STATUS current DESCRIPTION "The MAC address. This can not be changed. It represents an 802 MAC address as if it were transmitted least significant bit first. Format as six groups of 2 hexadecimal digits separated by colons (:) e.g. D0:22:12:B0:00:00" ::= { sdbDevIdEntry 8 } sdbDevIdUnitAddress OBJECT-TYPE SYNTAX Integer32 (0..65535) MAX-ACCESS read-write STATUS current DESCRIPTION "User defined address. This will be used for addressing the device on the databus." ::= { sdbDevIdEntry 9 } sdbDevIdName OBJECT-TYPE SYNTAX DisplayString (SIZE(0..16)) MAX-ACCESS read-write STATUS current DESCRIPTION "User configurable device name or identifier." ::= { sdbDevIdEntry 10 } sdbDevIdLocation OBJECT-TYPE SYNTAX DisplayString (SIZE(0..16)) MAX-ACCESS read-write STATUS current DESCRIPTION "User configurable device location identifier." ::= { sdbDevIdEntry 11 } sdbDevIdVanityTag OBJECT-TYPE SYNTAX DisplayString (SIZE(0..20)) MAX-ACCESS read-write STATUS current DESCRIPTION "Characters to be displayed as vanity text in display." ::= { sdbDevIdEntry 12 } sdbDevIdIndex OBJECT-TYPE SYNTAX Integer32 (1..65535) MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique value for each device. Its value represents the unit address of the device and is used to address individual devices in the tree. The value for each device will remain constant until the next scan is performed." ::= { sdbDevIdEntry 13 } sdbDevIdDeviceType OBJECT-TYPE SYNTAX INTEGER { pdu(0), dpm(1), hpdu-G3(2), dpm27e(3) } MAX-ACCESS read-only STATUS current DESCRIPTION "A unique value for each device group. Its value represents the device type of the device. Refer to manual for more information." ::= { sdbDevIdEntry 14 } sdbDevIdLocateUnit OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "The LCD-backlight flashes in a heartbeat rhythm to locate the unit." ::= { sdbDevIdEntry 15 } sdbDevIdConfigType OBJECT-TYPE SYNTAX Integer32 (0..256) MAX-ACCESS read-only STATUS current DESCRIPTION "Wiring configuration type used." ::= { sdbDevIdEntry 16 } sdbDevCfTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbDevCfEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table containing configuration information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices." ::= { sdbDevConfiguration 1 } sdbDevCfEntry OBJECT-TYPE SYNTAX SdbDevCfEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Configuration entry containing configuration objects of a particular databus device." INDEX { sdbDevIdIndex } ::= { sdbDevCfTable 1 } SdbDevCfEntry ::= SEQUENCE { sdbDevCfPhases Integer32, sdbDevCfOutletsTotal Integer32, sdbDevCfOutletsSwitched Integer32, sdbDevCfOutletsMetered Integer32, sdbDevCfSensors Integer32, sdbDevCfMaximumLoad Integer32, sdbDevCfBranches Integer32, sdbDevCfNeutral Integer32, sdbDevCfTempSensors Integer32, sdbDevCfTotals Integer32 } sdbDevCfPhases OBJECT-TYPE SYNTAX Integer32 (0 | 1 | 3) MAX-ACCESS read-only STATUS current DESCRIPTION "Number of phases for input metering." ::= { sdbDevCfEntry 1 } sdbDevCfOutletsTotal OBJECT-TYPE SYNTAX Integer32 (0..54) MAX-ACCESS read-only STATUS current DESCRIPTION "Total number of outlets including hardwired without switch/metered modules." ::= { sdbDevCfEntry 2 } sdbDevCfOutletsSwitched OBJECT-TYPE SYNTAX Integer32 (0..54) MAX-ACCESS read-only STATUS current DESCRIPTION "Number of switched outlets. If outlet numbering is non-contiguous its the highest outlet number." ::= { sdbDevCfEntry 3 } sdbDevCfOutletsMetered OBJECT-TYPE SYNTAX Integer32 (0..54) MAX-ACCESS read-only STATUS current DESCRIPTION "Number of metered outlets. If outlet numbering is non-contiguous its the highest outlet number." ::= { sdbDevCfEntry 4 } sdbDevCfSensors OBJECT-TYPE SYNTAX Integer32 (0..16) MAX-ACCESS read-only STATUS current DESCRIPTION "The number sensors." ::= { sdbDevCfEntry 5 } sdbDevCfMaximumLoad OBJECT-TYPE SYNTAX Integer32 (16 | 32) UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "Maximum rated load of device per phase" ::= { sdbDevCfEntry 6 } sdbDevCfBranches OBJECT-TYPE SYNTAX Integer32 (0..6) MAX-ACCESS read-only STATUS current DESCRIPTION "Number of branches for input metering." ::= { sdbDevCfEntry 7 } sdbDevCfNeutral OBJECT-TYPE SYNTAX Integer32 (0 | 1) MAX-ACCESS read-only STATUS current DESCRIPTION "Nuetral current measurement." ::= { sdbDevCfEntry 8 } sdbDevCfTempSensors OBJECT-TYPE SYNTAX Integer32 (0..16) MAX-ACCESS read-only STATUS current DESCRIPTION "Number of temperature sensors present in the system." ::= { sdbDevCfEntry 9 } sdbDevCfTotals OBJECT-TYPE SYNTAX Integer32 (0..16) MAX-ACCESS read-only STATUS current DESCRIPTION "The number of totals rows for the configuration." ::= { sdbDevCfEntry 10 } sdbDevSsTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbDevSsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table containing system status information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices." ::= { sdbDevSystemStatus 1 } sdbDevSsEntry OBJECT-TYPE SYNTAX SdbDevSsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "System status entry containing system status objects of a particular databus device." INDEX { sdbDevIdIndex } ::= { sdbDevSsTable 1 } SdbDevSsEntry ::= SEQUENCE { sdbDevSsDeviceStatusCode Integer32, sdbDevSsTemperatureAlert Integer32, sdbDevSsInputCurrentAlert Integer32, sdbDevSsOutletCurrentAlert Integer32, sdbDevSsInputVoltageAlert Integer32, sdbDevSsOutletCurrentDropAlert Integer32, sdbDevSsInputCurrentDropAlert Integer32, sdbDevSsSensorChangeAlert Integer32, sdbDevSsOutletVoltageDropAlert Integer32, sdbDevSsBranchCurrentAlert Integer32, sdbDevSsBranchVoltageAlert Integer32, sdbDevSsNeutralCurrentAlert Integer32, sdbDevSsResidualCurrentAlert Integer32, sdbDevSsHardwareAlert Integer32 } sdbDevSsDeviceStatusCode OBJECT-TYPE SYNTAX Integer32 (0..255) MAX-ACCESS read-only STATUS current DESCRIPTION "Returns an internal status or error code. A value of 0 means OK. If not 0 it can be any of the following codes. Multiple status codes can be active at the same time. The value will be the sum of the active status codes. 1 = alert flagged 2 = settings(s) initialized 4 = power-on reset 8 = external reset 16 = watchdog timer caused reset 32 = brownout detected 64 = controller error 128 = slave module was reset" ::= { sdbDevSsEntry 1 } sdbDevSsTemperatureAlert OBJECT-TYPE SYNTAX Integer32 (0..2) MAX-ACCESS read-only STATUS current DESCRIPTION "An alert has been raised due to temperature exceeding treshhold. 0 = no alert 1 = internal temperature sensor 2 = external temperature sensor" ::= { sdbDevSsEntry 2 } sdbDevSsInputCurrentAlert OBJECT-TYPE SYNTAX Integer32 (0..3) MAX-ACCESS read-only STATUS current DESCRIPTION "An alert has been raised due to current exceeding treshhold. The value indicates the exceeding phase. 0 = no alert." ::= { sdbDevSsEntry 3 } sdbDevSsOutletCurrentAlert OBJECT-TYPE SYNTAX Integer32 (0..54) MAX-ACCESS read-only STATUS current DESCRIPTION "An alert has been raised due to current exceeding treshhold. The value indicates the exceeding outlet. 0 = no alert." ::= { sdbDevSsEntry 4 } sdbDevSsInputVoltageAlert OBJECT-TYPE SYNTAX Integer32 (0..3) MAX-ACCESS read-only STATUS current DESCRIPTION "An alert has been raised due to a voltage dip. The value indicates the dipped phase. 0 = no alert." ::= { sdbDevSsEntry 5 } sdbDevSsOutletCurrentDropAlert OBJECT-TYPE SYNTAX Integer32 (0..54) MAX-ACCESS read-only STATUS current DESCRIPTION "An alert has been raised due to the current of a metered outlet suddenly dropping to near zero, possibly indicating a blown fuse. The value indicates the dropped outlet. 0 = no alert." ::= { sdbDevSsEntry 6 } sdbDevSsInputCurrentDropAlert OBJECT-TYPE SYNTAX Integer32 (0..3) MAX-ACCESS read-only STATUS current DESCRIPTION "An alert has been raised due to the current of a metered input suddenly dropping to near zero, possibly indicating a blown fuse. The value indicates the dropped phase. 0 = no alert." ::= { sdbDevSsEntry 7 } sdbDevSsSensorChangeAlert OBJECT-TYPE SYNTAX Integer32 (0..16) MAX-ACCESS read-only STATUS current DESCRIPTION "An alert has been raised due to a change in the number of sensors. The value indicates the previous amount of sensors." ::= { sdbDevSsEntry 8 } sdbDevSsOutletVoltageDropAlert OBJECT-TYPE SYNTAX Integer32 (0..54) MAX-ACCESS read-only STATUS current DESCRIPTION "An alert has been raised due to voltage drop on this outlet. The value indicates the first failed outlet." ::= { sdbDevSsEntry 9 } sdbDevSsBranchCurrentAlert OBJECT-TYPE SYNTAX Integer32 (0..18) MAX-ACCESS read-only STATUS current DESCRIPTION "An alert has been raised due to current exceeding treshhold. The value indicates the exceeding branch. 0 = no alert." ::= { sdbDevSsEntry 10 } sdbDevSsBranchVoltageAlert OBJECT-TYPE SYNTAX Integer32 (0..18) MAX-ACCESS read-only STATUS current DESCRIPTION "An alert has been raised due to a voltage dip. The value indicates the dipped branch. 0 = no alert." ::= { sdbDevSsEntry 11 } sdbDevSsNeutralCurrentAlert OBJECT-TYPE SYNTAX Integer32 (0..1) MAX-ACCESS read-only STATUS current DESCRIPTION "An alert has been raised due to current exceeding treshhold. 0 = no alert 1 = current alert" ::= { sdbDevSsEntry 12 } sdbDevSsResidualCurrentAlert OBJECT-TYPE SYNTAX Integer32 (0..2) MAX-ACCESS read-only STATUS current DESCRIPTION "A residual current alert has been raised. 0 = no alert 1 = current exceeding treshhold alert 2 = sensor error" ::= { sdbDevSsEntry 13 } sdbDevSsHardwareAlert OBJECT-TYPE SYNTAX Integer32 (0..9) MAX-ACCESS read-only STATUS current DESCRIPTION "0 = no alarm >0 = or slave number for alert" ::= { sdbDevSsEntry 14 } sdbDevRsTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbDevRsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table providing reset capabilities to devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices." ::= { sdbDevReset 1 } sdbDevRsEntry OBJECT-TYPE SYNTAX SdbDevRsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Reset entry providing reset objects of a particular databus device." INDEX { sdbDevIdIndex } ::= { sdbDevRsTable 1 } SdbDevRsEntry ::= SEQUENCE { sdbDevRsReboot Integer32, sdbDevRsResetAlerts Integer32, sdbDevRsZeroInputKWhSubtotal Integer32, sdbDevRsZeroOutletKWhSubtotal Integer32, sdbDevRsResetPeaksAndDips Integer32 } sdbDevRsReboot OBJECT-TYPE SYNTAX INTEGER { idle(0), reboot(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Warm reboot/reset of device controller. NOTE: this will have NO effect on outlet status!" ::= { sdbDevRsEntry 1 } sdbDevRsResetAlerts OBJECT-TYPE SYNTAX INTEGER { idle(0), reset(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Reset all alert signals and device status code." ::= { sdbDevRsEntry 2 } sdbDevRsZeroInputKWhSubtotal OBJECT-TYPE SYNTAX INTEGER { idle(0), zero(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Reset of all input kWh subtotal counters to zero." ::= { sdbDevRsEntry 3 } sdbDevRsZeroOutletKWhSubtotal OBJECT-TYPE SYNTAX INTEGER { idle(0), zero(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Reset of all outlet kWh subtotal counter to zero." ::= { sdbDevRsEntry 4 } sdbDevRsResetPeaksAndDips OBJECT-TYPE SYNTAX INTEGER { idle(0), reset(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Reset all peak and dip values to zero." ::= { sdbDevRsEntry 5 } sdbDevStTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbDevStEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table containing setting information of devices connected to the databus. The number of entries is given by the value of sdbMgmtStsAddressableDevices." ::= { sdbDevSettings 1 } sdbDevStEntry OBJECT-TYPE SYNTAX SdbDevStEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Setting entry containing settings objects of a particular databus device." INDEX { sdbDevIdIndex } ::= { sdbDevStTable 1 } SdbDevStEntry ::= SEQUENCE { sdbDevStAutoResetAlerts Integer32, sdbDevStExtendedNames Integer32, sdbDevStPeakDuration MilliSecond, sdbDevStFixedOutletDelay MilliSecond, sdbDevStPowerSaverMode Second, sdbDevStOutletPowerUpMode Integer32, sdbDevStMaximumTemperature Integer32, sdbDevStDisplayOrientation Integer32, sdbDevStLocalAlertReset Integer32, sdbDevStCurrentDropDetection Integer32, sdbDevStUsbMode Integer32, sdbDevStSensorChangeAlertMode Integer32, sdbDevStOutletUnlockOverride Integer32 } sdbDevStAutoResetAlerts OBJECT-TYPE SYNTAX Integer32 (0..65535) UNITS "seconds" MAX-ACCESS read-write STATUS current DESCRIPTION "Auto reset alerts configuration. If set to 0 the auto reset alerts feature is disabled. If set to a value greater then 0, the auto reset alerts feature is enabled and alerts will get cleared after the configured amount of seconds since the last alert condition have passed." ::= { sdbDevStEntry 2 } sdbDevStExtendedNames OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Use original or longer names for inputs, outlets and sensors." ::= { sdbDevStEntry 3 } sdbDevStPeakDuration OBJECT-TYPE SYNTAX MilliSecond (0..65535) UNITS "ms" MAX-ACCESS read-write STATUS current DESCRIPTION "Amount of ms a current peak should last before an alert is raised." ::= { sdbDevStEntry 4 } sdbDevStFixedOutletDelay OBJECT-TYPE SYNTAX MilliSecond (100..65535) UNITS "ms" MAX-ACCESS read-write STATUS current DESCRIPTION "Minimal delay between two successive relay switches in milliseconds. Minimal delay is 100 ms. Will always be respected!" ::= { sdbDevStEntry 5 } sdbDevStPowerSaverMode OBJECT-TYPE SYNTAX Second (0 | 10 | 60 | 120 | 240) UNITS "s" MAX-ACCESS read-write STATUS current DESCRIPTION "Set backlight on time in seconds. 0 keeps display always on. Note that keeping the backlight on may decrease luminosity over time." ::= { sdbDevStEntry 6 } sdbDevStOutletPowerUpMode OBJECT-TYPE SYNTAX INTEGER { off(0), -- off sameState(1), -- same state as at power down sameStateDelayed(2) -- same state as at power down but delayed by -- individual delay timer. } MAX-ACCESS read-write STATUS current DESCRIPTION "Behaviour of outlets on power-up." ::= { sdbDevStEntry 7 } sdbDevStMaximumTemperature OBJECT-TYPE SYNTAX Integer32 (0..99) UNITS "degrees Celsius" MAX-ACCESS read-write STATUS current DESCRIPTION "Maximum temperature threshold An alert will be generated whenever the temperature is above this value. Zero means disabled." ::= { sdbDevStEntry 8 } sdbDevStDisplayOrientation OBJECT-TYPE SYNTAX INTEGER { noDisplay(0), verticalDisplayOnTop(1), verticalDisplayUpsideDown(2), horizontalDisplayAtLeft(3), horizontalDisplayAtRight(4) } MAX-ACCESS read-write STATUS current DESCRIPTION "Display orientation." ::= { sdbDevStEntry 9 } sdbDevStLocalAlertReset OBJECT-TYPE SYNTAX INTEGER { notAllowed(0), allowed(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Allow alerts to be reset locally on device by pushing one of the buttons." ::= { sdbDevStEntry 10 } sdbDevStCurrentDropDetection OBJECT-TYPE SYNTAX INTEGER { off(0), inputsOnly(1), outletsOnly(2), inputsAndOutlets(3) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enables the current drop detection function." ::= { sdbDevStEntry 11 } sdbDevStUsbMode OBJECT-TYPE SYNTAX INTEGER { usbDisabled(0), onlyFirmwareUpdates(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Allow the USB port to be used for specific tasks" ::= { sdbDevStEntry 13 } sdbDevStSensorChangeAlertMode OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Enable sensoe change alerts" ::= { sdbDevStEntry 14 } sdbDevStOutletUnlockOverride OBJECT-TYPE SYNTAX INTEGER { disabled(0), enabled(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Overrides the timeout. If this is set to 1 then the timeout will be ignored, otherwise the timeout will be taken into account." ::= { sdbDevStEntry 15 } sdbDevInTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbDevInEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table containing information of inputs of devices connected to the databus." ::= { sdbDevInput 1 } sdbDevInEntry OBJECT-TYPE SYNTAX SdbDevInEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Inputs entry containing objects of an input of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevInIndex to identify a particular input of the device identified by sdbDevIdIndex." INDEX { sdbDevIdIndex, sdbDevInIndex } ::= { sdbDevInTable 1 } SdbDevInEntry ::= SEQUENCE { sdbDevInIndex Integer32, sdbDevInKWhTotal KiloWattHour, sdbDevInKWhSubtotal KiloWattHour, sdbDevInPowerFactor CentiPercent, sdbDevInActualCurrent CentiAmpere, sdbDevInPeakCurrent CentiAmpere, sdbDevInActualVoltage CentiVolt, sdbDevInMinVoltage CentiVolt, sdbDevInPowerVoltAmpere Integer32, sdbDevInPowerWatt Integer32, sdbDevInMaxAmps CentiAmpere, sdbDevInCTRatio Integer32, sdbDevInName DisplayString, sdbDevInZeroKWhSubtotal Integer32 } sdbDevInIndex OBJECT-TYPE SYNTAX Integer32 (1..54) MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique value for each input. Its value ranges between 1 and the value of sdbDevCfPhases." ::= { sdbDevInEntry 1 } sdbDevInKWhTotal OBJECT-TYPE SYNTAX KiloWattHour UNITS "kWh" MAX-ACCESS read-only STATUS current DESCRIPTION "Total kWh value of an input. This value can not be reset." ::= { sdbDevInEntry 2 } sdbDevInKWhSubtotal OBJECT-TYPE SYNTAX KiloWattHour UNITS "kWh" MAX-ACCESS read-only STATUS current DESCRIPTION "Subtotal kWh value of an input. This value can be reset." ::= { sdbDevInEntry 3 } sdbDevInPowerFactor OBJECT-TYPE SYNTAX CentiPercent UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Power factor of input. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between 0 and 1. This value is expressed as a percentage between 0% and 100%." ::= { sdbDevInEntry 4 } sdbDevInActualCurrent OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "Actual apparent, RMS current." ::= { sdbDevInEntry 5 } sdbDevInPeakCurrent OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak apparent, RMS current. Highest value since last reset of the alerts." ::= { sdbDevInEntry 6 } sdbDevInActualVoltage OBJECT-TYPE SYNTAX CentiVolt UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "The actual voltage." ::= { sdbDevInEntry 7 } sdbDevInMinVoltage OBJECT-TYPE SYNTAX CentiVolt UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "RMS voltage dip. Lowest value since reset of alerts." ::= { sdbDevInEntry 8 } sdbDevInPowerVoltAmpere OBJECT-TYPE SYNTAX Integer32 (0..327680) UNITS "VA" MAX-ACCESS read-only STATUS current DESCRIPTION "Calculated apparent power." ::= { sdbDevInEntry 9 } sdbDevInPowerWatt OBJECT-TYPE SYNTAX Integer32 (0..327680) UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "Calculated real power." ::= { sdbDevInEntry 10 } sdbDevInMaxAmps OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-write STATUS current DESCRIPTION "Maximum current per input phase. Should last at least sdbDevStPeakDuration ms before triggering an alert." ::= { sdbDevInEntry 11 } sdbDevInCTRatio OBJECT-TYPE SYNTAX Integer32 (0..255) MAX-ACCESS read-write STATUS current DESCRIPTION "The multiplier to use for the input CTs." ::= { sdbDevInEntry 12 } sdbDevInName OBJECT-TYPE SYNTAX DisplayString (SIZE(0..8)) MAX-ACCESS read-write STATUS current DESCRIPTION "User configurable naming of inputs or phases." ::= { sdbDevInEntry 13 } sdbDevInZeroKWhSubtotal OBJECT-TYPE SYNTAX INTEGER { idle(0), zero(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Reset input kWh subtotal counter of a single input to zero." ::= { sdbDevInEntry 14 } sdbDevOutTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbDevOutEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table containing information of outlets of devices connected to the databus." ::= { sdbDevOutlet 1 } sdbDevOutEntry OBJECT-TYPE SYNTAX SdbDevOutEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Outlets entry containing objects of an outlet of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevOutIndex to identify a particular outlet of the device identified by sdbDevIdIndex." INDEX { sdbDevIdIndex, sdbDevOutIndex } ::= { sdbDevOutTable 1 } SdbDevOutEntry ::= SEQUENCE { sdbDevOutIndex Integer32, sdbDevOutName DisplayString } sdbDevOutIndex OBJECT-TYPE SYNTAX Integer32 (1..54) MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique value for each outlet. Its value ranges between 1 and the value of sdbDevCfOutletsTotal." ::= { sdbDevOutEntry 1 } sdbDevOutName OBJECT-TYPE SYNTAX DisplayString (SIZE(0..8)) MAX-ACCESS read-write STATUS current DESCRIPTION "User configurable naming of individual outlets." ::= { sdbDevOutEntry 2 } sdbDevOutMtTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbDevOutMtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table containing information of metered outlets of devices connected to the databus." ::= { sdbDevOutlet 2 } sdbDevOutMtEntry OBJECT-TYPE SYNTAX SdbDevOutMtEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Metered outlets entry containing objects of a metered outlet of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevOutMtIndex to identify a particular outlet of the device identified by sdbDevIdIndex." INDEX { sdbDevIdIndex, sdbDevOutMtIndex } ::= { sdbDevOutMtTable 1 } SdbDevOutMtEntry ::= SEQUENCE { sdbDevOutMtIndex Integer32, sdbDevOutMtKWhTotal KiloWattHour, sdbDevOutMtKWhSubtotal KiloWattHour, sdbDevOutMtPowerFactor CentiPercent, sdbDevOutMtActualCurrent CentiAmpere, sdbDevOutMtPeakCurrent CentiAmpere, sdbDevOutMtActualVoltage CentiVolt, sdbDevOutMtMaxAmps CentiAmpere, sdbDevOutMtCTRatio Integer32, sdbDevOutMtPowerVoltAmpere Integer32, sdbDevOutMtPowerWatt Integer32 } sdbDevOutMtIndex OBJECT-TYPE SYNTAX Integer32 (1..54) MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique value for each outlet. Its value ranges between 1 and the value of sdbDevCfOutletsMetered." ::= { sdbDevOutMtEntry 1 } sdbDevOutMtKWhTotal OBJECT-TYPE SYNTAX KiloWattHour UNITS "kWh" MAX-ACCESS read-only STATUS current DESCRIPTION "Total kWh value of an outlet. This value can not be reset." ::= { sdbDevOutMtEntry 2 } sdbDevOutMtKWhSubtotal OBJECT-TYPE SYNTAX KiloWattHour UNITS "kWh" MAX-ACCESS read-only STATUS current DESCRIPTION "Subotal kWh value of an outlet. This value can be reset." ::= { sdbDevOutMtEntry 3 } sdbDevOutMtPowerFactor OBJECT-TYPE SYNTAX CentiPercent UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Power factor of outlet. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between 0 and 1. This number is expressed as a percentage between 0% and 100%." ::= { sdbDevOutMtEntry 4 } sdbDevOutMtActualCurrent OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "Actual apparent, RMS current." ::= { sdbDevOutMtEntry 5 } sdbDevOutMtPeakCurrent OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak apparent, RMS current. Highest value since last reset of the alerts." ::= { sdbDevOutMtEntry 6 } sdbDevOutMtActualVoltage OBJECT-TYPE SYNTAX CentiVolt UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "Actual voltage on outlet." ::= { sdbDevOutMtEntry 7 } sdbDevOutMtMaxAmps OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-write STATUS current DESCRIPTION "Maximum current per outlet. Should last at least sdbDevStPeakDuration ms before triggering an alert." ::= { sdbDevOutMtEntry 8 } sdbDevOutMtCTRatio OBJECT-TYPE SYNTAX Integer32 (0..255) MAX-ACCESS read-write STATUS current DESCRIPTION "The multiplier to use for the outlet CTs." ::= { sdbDevOutMtEntry 9 } sdbDevOutMtPowerVoltAmpere OBJECT-TYPE SYNTAX Integer32 (0..327680) UNITS "VA" MAX-ACCESS read-only STATUS current DESCRIPTION "Calculated apparent power." ::= { sdbDevOutMtEntry 10 } sdbDevOutMtPowerWatt OBJECT-TYPE SYNTAX Integer32 (0..327680) UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "Calculated real power." ::= { sdbDevOutMtEntry 11 } sdbDevOutSwTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbDevOutSwEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table containing information of switched outlets of devices connected to the databus." ::= { sdbDevOutlet 3 } sdbDevOutSwEntry OBJECT-TYPE SYNTAX SdbDevOutSwEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Switched outlets entry containing objects of a switched outlet of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevOutSwIndex to identify a particular outlet of the device identified by sdbDevIdIndex." INDEX { sdbDevIdIndex, sdbDevOutSwIndex } ::= { sdbDevOutSwTable 1 } SdbDevOutSwEntry ::= SEQUENCE { sdbDevOutSwIndex Integer32, sdbDevOutSwCurrentState Integer32, sdbDevOutSwScheduled Integer32, sdbDevOutSwUnlock Integer32, sdbDevOutSwIndividualOutletDelay Second, sdbDevOutSwReboot Integer32 } sdbDevOutSwIndex OBJECT-TYPE SYNTAX Integer32 (1..54) MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique value for each outlet. Its value ranges between 1 and the value of sdbDevCfOutletsSwitched." ::= { sdbDevOutSwEntry 1 } sdbDevOutSwCurrentState OBJECT-TYPE SYNTAX INTEGER { off(0), on(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "The actual state of the outlet relay. Note that Writing is only effective after setting sdbDevOutSwUnlock." ::= { sdbDevOutSwEntry 2 } sdbDevOutSwScheduled OBJECT-TYPE SYNTAX INTEGER { idle(0), scheduled(1) } MAX-ACCESS read-only STATUS current DESCRIPTION "A one indicates pending activity; the switch delay has not yet expired." ::= { sdbDevOutSwEntry 3 } sdbDevOutSwUnlock OBJECT-TYPE SYNTAX INTEGER { locked(0), unlocked(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Switching and rebooting is unlocked for 10 seconds by writing a 1." ::= { sdbDevOutSwEntry 4 } sdbDevOutSwIndividualOutletDelay OBJECT-TYPE SYNTAX Second (0..65535) UNITS "s" MAX-ACCESS read-write STATUS current DESCRIPTION "Delay before an individual outlet switches on at power-up." ::= { sdbDevOutSwEntry 5 } sdbDevOutSwReboot OBJECT-TYPE SYNTAX INTEGER { idle(0), reboot(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Reboot outlet relay if current state is on and outlet is unlocked; The outlet will be turned on after 10 seconds." ::= { sdbDevOutSwEntry 6 } sdbDevMeasuresTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbDevMeasuresEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table containing information of temperatures of devices connected to the databus." ::= { sdbDevSensor 1 } sdbDevMeasuresEntry OBJECT-TYPE SYNTAX SdbDevMeasuresEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Device measures entry containing temperature information objects of a particular databus device." INDEX { sdbDevIdIndex } ::= { sdbDevMeasuresTable 1 } SdbDevMeasuresEntry ::= SEQUENCE { sdbDevMsIntTemperature CentiCelsius, sdbDevMsExtTemperature CentiCelsius, sdbDevMsIntTemperaturePeak CentiCelsius, sdbDevMsExtTemperaturePeak CentiCelsius, sdbDevMsResidualCurrent CentiAmpere, sdbDevMsResidualPeak CentiAmpere } sdbDevMsIntTemperature OBJECT-TYPE SYNTAX CentiCelsius UNITS "degrees Celsius" MAX-ACCESS read-only STATUS current DESCRIPTION "Actual internal device temperature in deg C" ::= { sdbDevMeasuresEntry 1 } sdbDevMsExtTemperature OBJECT-TYPE SYNTAX CentiCelsius UNITS "degrees Celsius" MAX-ACCESS read-only STATUS current DESCRIPTION "Actual external device temperature sensor in deg C." ::= { sdbDevMeasuresEntry 2 } sdbDevMsIntTemperaturePeak OBJECT-TYPE SYNTAX CentiCelsius UNITS "degrees Celsius" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak internal device temperature since last reset of alerts." ::= { sdbDevMeasuresEntry 3 } sdbDevMsExtTemperaturePeak OBJECT-TYPE SYNTAX CentiCelsius UNITS "degrees Celsius" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak external device temperature since last reset of alerts." ::= { sdbDevMeasuresEntry 4 } sdbDevMsResidualCurrent OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "Residual current." ::= { sdbDevMeasuresEntry 5 } sdbDevMsResidualPeak OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak residual current." ::= { sdbDevMeasuresEntry 6 } sdbDevSnsTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbDevSnsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table containing information of sensors of devices connected to the databus." ::= { sdbDevSensor 2 } sdbDevSnsEntry OBJECT-TYPE SYNTAX SdbDevSnsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Sensors entry containing objects of a sensor of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevSnsIndex to identify a particular sensor of the device identified by sdbDevIdIndex." INDEX { sdbDevIdIndex, sdbDevSnsIndex } ::= { sdbDevSnsTable 1 } SdbDevSnsEntry ::= SEQUENCE { sdbDevSnsIndex Integer32, sdbDevSnsType DisplayString, sdbDevSnsValue CentiValue, sdbDevSnsName DisplayString } sdbDevSnsIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique value for each sensor. Its value ranges between 1 and the value of sdbDevCfSensors." ::= { sdbDevSnsEntry 1 } sdbDevSnsType OBJECT-TYPE SYNTAX DisplayString (SIZE(1)) MAX-ACCESS read-only STATUS current DESCRIPTION "Type of connected sensor. T = Temperature (C) H = Humidity (%) I = dry switch contact" ::= { sdbDevSnsEntry 2 } sdbDevSnsValue OBJECT-TYPE SYNTAX CentiValue (0..327680) MAX-ACCESS read-only STATUS current DESCRIPTION "Value of connected sensor" ::= { sdbDevSnsEntry 3 } sdbDevSnsName OBJECT-TYPE SYNTAX DisplayString (SIZE(0..18)) MAX-ACCESS read-write STATUS current DESCRIPTION "User definable name for sensors." ::= { sdbDevSnsEntry 4 } -- --------------------------------------------------------------------------------------------- sdbDevPerformanceTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbDevPerformanceEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table containing information of sensors of devices connected to the databus." ::= { sdbDevPerformance 1 } sdbDevPerformanceEntry OBJECT-TYPE SYNTAX SdbDevPerformanceEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Performance counters of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevPerformanceIndex to identify a particular counter of the device identified by sdbDevIdIndex." INDEX { sdbDevIdIndex, sdbDevPerformanceIndex } ::= { sdbDevPerformanceTable 1 } SdbDevPerformanceEntry ::= SEQUENCE { sdbDevPerformanceIndex Integer32, sdbDevPerformanceValue Integer32, sdbDevPerformanceMax Integer32, sdbDevPerformanceLimit Integer32, sdbDevPerformanceName DisplayString } sdbDevPerformanceIndex OBJECT-TYPE SYNTAX Integer32 (1..16) MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique value for each counter. Its value ranges between 1 and 16." ::= { sdbDevPerformanceEntry 1 } sdbDevPerformanceValue OBJECT-TYPE SYNTAX Integer32 (0..16777215) MAX-ACCESS read-only STATUS current DESCRIPTION "Value of counter" ::= { sdbDevPerformanceEntry 2 } sdbDevPerformanceMax OBJECT-TYPE SYNTAX Integer32 (0..16777215) MAX-ACCESS read-only STATUS current DESCRIPTION "Max of counter" ::= { sdbDevPerformanceEntry 3 } sdbDevPerformanceLimit OBJECT-TYPE SYNTAX Integer32 (0..16777215) MAX-ACCESS read-only STATUS current DESCRIPTION "Limit of counter" ::= { sdbDevPerformanceEntry 4 } sdbDevPerformanceName OBJECT-TYPE SYNTAX DisplayString (SIZE(0..12)) MAX-ACCESS read-write STATUS current DESCRIPTION "User definable name for counter." ::= { sdbDevPerformanceEntry 5 } -- --------------------------------------------------------------------------------------------- sdbDevPerformanceResetTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbDevPerformanceResetEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table containing the last reset reason of the device" ::= { sdbDevPerformance 2 } sdbDevPerformanceResetEntry OBJECT-TYPE SYNTAX SdbDevPerformanceResetEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Setting entry containing settings objects of a particular databus device." INDEX { sdbDevIdIndex } ::= { sdbDevPerformanceResetTable 1 } SdbDevPerformanceResetEntry ::= SEQUENCE { sdbDevPerformanceResetReason DisplayString, sdbDevResetUptime Unsigned32 } sdbDevPerformanceResetReason OBJECT-TYPE SYNTAX DisplayString (SIZE(0..64)) MAX-ACCESS read-write STATUS current DESCRIPTION "Last reset reason." ::= { sdbDevPerformanceResetEntry 1 } sdbDevResetUptime OBJECT-TYPE SYNTAX Unsigned32 MAX-ACCESS read-only STATUS current DESCRIPTION "Uptime before last reset" ::= { sdbDevPerformanceResetEntry 2 } -- --------------------------------------------------------------------------------------------- sdbDevBranchTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbDevBranchEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table containing information of inputs of devices connected to the databus." ::= { sdbDevBranches 1 } sdbDevBranchEntry OBJECT-TYPE SYNTAX SdbDevBranchEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Inputs entry containing objects of an input of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevBranchIndex to identify a particular input of the device identified by sdbDevIdIndex." INDEX { sdbDevIdIndex, sdbDevBranchIndex } ::= { sdbDevBranchTable 1 } SdbDevBranchEntry ::= SEQUENCE { sdbDevBranchIndex Integer32, sdbDevBranchKWhTotal KiloWattHour, sdbDevBranchKWhSubtotal KiloWattHour, sdbDevBranchPowerFactor CentiPercent, sdbDevBranchActualCurrent CentiAmpere, sdbDevBranchPeakCurrent CentiAmpere, sdbDevBranchActualVoltage CentiVolt, sdbDevBranchMinVoltage CentiVolt, sdbDevBranchPowerVoltAmpere Integer32, sdbDevBranchPowerWatt Integer32, sdbDevBranchMaxAmps CentiAmpere, sdbDevBranchCTRatio Integer32, sdbDevBranchName DisplayString, sdbDevBranchZeroKWhSubtotal Integer32 } sdbDevBranchIndex OBJECT-TYPE SYNTAX Integer32 (1..54) MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique value for each input. Its value ranges between 1 and the value of sdbDevCfPhases." ::= { sdbDevBranchEntry 1 } sdbDevBranchKWhTotal OBJECT-TYPE SYNTAX KiloWattHour UNITS "kWh" MAX-ACCESS read-only STATUS current DESCRIPTION "Total kWh value of an input. This value can not be reset." ::= { sdbDevBranchEntry 2 } sdbDevBranchKWhSubtotal OBJECT-TYPE SYNTAX KiloWattHour UNITS "kWh" MAX-ACCESS read-only STATUS current DESCRIPTION "Subtotal kWh value of an input. This value can be reset." ::= { sdbDevBranchEntry 3 } sdbDevBranchPowerFactor OBJECT-TYPE SYNTAX CentiPercent UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Power factor of input. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between 0 and 1. This value is expressed as a percentage between 0% and 100%." ::= { sdbDevBranchEntry 4 } sdbDevBranchActualCurrent OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "Actual apparent, RMS current." ::= { sdbDevBranchEntry 5 } sdbDevBranchPeakCurrent OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak apparent, RMS current. Highest value since last reset of the alerts." ::= { sdbDevBranchEntry 6 } sdbDevBranchActualVoltage OBJECT-TYPE SYNTAX CentiVolt UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "The actual voltage." ::= { sdbDevBranchEntry 7 } sdbDevBranchMinVoltage OBJECT-TYPE SYNTAX CentiVolt UNITS "V" MAX-ACCESS read-only STATUS current DESCRIPTION "RMS voltage dip. Lowest value since reset of alerts." ::= { sdbDevBranchEntry 8 } sdbDevBranchPowerVoltAmpere OBJECT-TYPE SYNTAX Integer32 (0..327680) UNITS "VA" MAX-ACCESS read-only STATUS current DESCRIPTION "Calculated apparent power." ::= { sdbDevBranchEntry 9 } sdbDevBranchPowerWatt OBJECT-TYPE SYNTAX Integer32 (0..327680) UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "Calculated real power." ::= { sdbDevBranchEntry 10 } sdbDevBranchMaxAmps OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-write STATUS current DESCRIPTION "Maximum current per input phase. Should last at least sdbDevStPeakDuration ms before triggering an alert." ::= { sdbDevBranchEntry 11 } sdbDevBranchCTRatio OBJECT-TYPE SYNTAX Integer32 (0..255) MAX-ACCESS read-write STATUS current DESCRIPTION "The multiplier to use for the input CTs." ::= { sdbDevBranchEntry 12 } sdbDevBranchName OBJECT-TYPE SYNTAX DisplayString (SIZE(0..8)) MAX-ACCESS read-write STATUS current DESCRIPTION "User configurable naming of branches." ::= { sdbDevBranchEntry 13 } sdbDevBranchZeroKWhSubtotal OBJECT-TYPE SYNTAX INTEGER { idle(0), zero(1) } MAX-ACCESS read-write STATUS current DESCRIPTION "Reset input kWh subtotal counter of a single input to zero." ::= { sdbDevBranchEntry 14 } -- --------------------------------------------------------------------------------------------- sdbDevTotalsTable OBJECT-TYPE SYNTAX SEQUENCE OF SdbDevTotalsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "A table containing information of inputs of devices connected to the databus." ::= { sdbDevTotals 1 } sdbDevTotalsEntry OBJECT-TYPE SYNTAX SdbDevTotalsEntry MAX-ACCESS not-accessible STATUS current DESCRIPTION "Inputs entry containing objects of an input of a particular databus device. Note that this table has two indexes. sdbDevIdIndex to identify a particular device and sdbDevTotalsIndex to identify a particular input of the device identified by sdbDevIdIndex." INDEX { sdbDevIdIndex, sdbDevTotalsIndex } ::= { sdbDevTotalsTable 1 } SdbDevTotalsEntry ::= SEQUENCE { sdbDevTotalsIndex Integer32, sdbDevTotalsKWhTotal KiloWattHour, sdbDevTotalsPowerFactor CentiPercent, sdbDevTotalsActualCurrent CentiAmpere, sdbDevTotalsPeakCurrent CentiAmpere, sdbDevTotalsPowerVoltAmpere Integer32, sdbDevTotalsPowerWatt Integer32, sdbDevTotalsNeutralCurrent CentiAmpere, sdbDevTotalsNeutralPeak CentiAmpere, sdbDevTotalsNeutralMaxAmps CentiAmpere, sdbDevTotalsResidualMaxAmps CentiAmpere } sdbDevTotalsIndex OBJECT-TYPE SYNTAX Integer32 (1..54) MAX-ACCESS not-accessible STATUS current DESCRIPTION "A unique value for each input. Its value ranges between 1 and the value of sdbDevCfPhases." ::= { sdbDevTotalsEntry 1 } sdbDevTotalsKWhTotal OBJECT-TYPE SYNTAX KiloWattHour UNITS "kWh" MAX-ACCESS read-only STATUS current DESCRIPTION "Total kWh value of an input. This value can not be reset." ::= { sdbDevTotalsEntry 2 } sdbDevTotalsPowerFactor OBJECT-TYPE SYNTAX CentiPercent UNITS "%" MAX-ACCESS read-only STATUS current DESCRIPTION "Power factor of input. The power factor of an AC power system is defined as the ratio of the real or active power to the apparent power and is a number between 0 and 1. This value is expressed as a percentage between 0% and 100%." ::= { sdbDevTotalsEntry 3 } sdbDevTotalsActualCurrent OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "Actual apparent, RMS current." ::= { sdbDevTotalsEntry 4 } sdbDevTotalsPeakCurrent OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak apparent, RMS current. Highest value since last reset of the alerts." ::= { sdbDevTotalsEntry 5 } sdbDevTotalsPowerVoltAmpere OBJECT-TYPE SYNTAX Integer32 (0..327680) UNITS "VA" MAX-ACCESS read-only STATUS current DESCRIPTION "Calculated apparent power." ::= { sdbDevTotalsEntry 6 } sdbDevTotalsPowerWatt OBJECT-TYPE SYNTAX Integer32 (0..327680) UNITS "W" MAX-ACCESS read-only STATUS current DESCRIPTION "Calculated real power." ::= { sdbDevTotalsEntry 7 } sdbDevTotalsNeutralCurrent OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "Neutral current of phases." ::= { sdbDevTotalsEntry 8 } sdbDevTotalsNeutralPeak OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-only STATUS current DESCRIPTION "Peak neutral current of phases." ::= { sdbDevTotalsEntry 9 } sdbDevTotalsNeutralMaxAmps OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-write STATUS current DESCRIPTION "Maximum neutral current. Should last at least sdbDevStPeakDuration ms before triggering an alert." ::= { sdbDevTotalsEntry 10 } sdbDevTotalsResidualMaxAmps OBJECT-TYPE SYNTAX CentiAmpere UNITS "A" MAX-ACCESS read-write STATUS current DESCRIPTION "Maximum residual current. Should last at least sdbDevStPeakDuration ms before triggering an alert." ::= { sdbDevTotalsEntry 11 } -- --------------------------------------------------------------------------------------------- sdbDevSsDeviceStatusCodeChanged NOTIFICATION-TYPE STATUS current DESCRIPTION "Device status code changed. OBJECTS { sdbDevSsDeviceStatusCode }" ::= { sdbMIBNotifications 1 } sdbDevSsTemperatureAlertDetected NOTIFICATION-TYPE STATUS current DESCRIPTION "Temperature alert detected. Internal temperature alert: OBJECTS { sdbDevSsTemperatureAlert, sdbDevMsIntTemperature, sdbDevMsIntTemperaturePeak } External analog temperature alert: OBJECTS { sdbDevSsTemperatureAlert, sdbDevMsExtTemperature, sdbDevMsExtTemperaturePeak } External digital temperature alert: OBJECTS { sdbDevSsTemperatureAlert, sdbDevSnsValue }" ::= { sdbMIBNotifications 2 } sdbDevSsInputCurrentAlertDetected NOTIFICATION-TYPE STATUS current DESCRIPTION "Input current alert detected. OBJECTS { sdbDevSsInputCurrentAlert, sdbDevInActualCurrent }" ::= { sdbMIBNotifications 3 } sdbDevSsOutletCurrentAlertDetected NOTIFICATION-TYPE STATUS current DESCRIPTION "Outlet current alert detected. OBJECTS { sdbDevSsOutletCurrentAlert, sdbDevOutMtActualCurrent }" ::= { sdbMIBNotifications 4 } sdbDevSsInputVoltageAlertDetected NOTIFICATION-TYPE STATUS current DESCRIPTION "Input voltage alert detected. OBJECTS { sdbDevSsInputVoltageAlert, sdbDevInActualVoltage }" ::= { sdbMIBNotifications 5 } sdbDevSsOutletCurrentDropAlertDetected NOTIFICATION-TYPE STATUS current DESCRIPTION "Outlet current drop alert detected. OBJECTS { sdbDevSsOutletCurrentDropAlert, sdbDevOutMtActualCurrent }" ::= { sdbMIBNotifications 6 } sdbDevSsInputCurrentDropAlertDetected NOTIFICATION-TYPE STATUS current DESCRIPTION "Input current drop alert detected. OBJECTS { sdbDevSsInputCurrentDropAlert, sdbDevInActualCurrent }" ::= { sdbMIBNotifications 7 } sdbDevSsSensorChangeAlertDetected NOTIFICATION-TYPE STATUS current DESCRIPTION "Sensor channel change alert detected. OBJECTS { sdbDevSsSensorChangeAlert }" ::= { sdbMIBNotifications 8 } sdbMgmtStsRingStateChanged NOTIFICATION-TYPE STATUS current DESCRIPTION "Ring state changed. Ring state changded to open: OBJECTS { sdbMgmtStsRingState, sdbMgmtStsRingBreachIndex } Ring state changded to closed: OBJECTS { sdbMgmtStsRingState }" ::= { sdbMIBNotifications 9 } sdbDevSsOutletVoltageDropAlertDetected NOTIFICATION-TYPE STATUS current DESCRIPTION "Outlet voltage drop alert detected. OBJECTS { sdbDevSsOutletVoltageDropAlert, sdbDevOutMtActualVoltage }" ::= { sdbMIBNotifications 10 } sdbDevSsBranchCurrentAlertDetected NOTIFICATION-TYPE STATUS current DESCRIPTION "Branch current alert detected. OBJECTS { sdbDevSsBranchCurrentAlert, sdbDevBranchActualCurrent }" ::= { sdbMIBNotifications 11 } sdbDevSsBranchVoltageAlertDetected NOTIFICATION-TYPE STATUS current DESCRIPTION "Branch current alert detected. OBJECTS { sdbDevSsBranchVoltageAlert, sdbDevBranchActualVoltage }" ::= { sdbMIBNotifications 12 } sdbDevSsNeutralCurrentAlertDetected NOTIFICATION-TYPE STATUS current DESCRIPTION "Input current alert detected. OBJECTS { sdbDevSsNeutralCurrentAlert, sdbDevTotalsNeutralCurrent }" ::= { sdbMIBNotifications 13 } sdbDevSsResidualCurrentAlertDetected NOTIFICATION-TYPE STATUS current DESCRIPTION "Residual current alert detected. OBJECTS { sdbDevSsResidualCurrentAlert, sdbDevMsResidualCurrent, sdbDevMsResidualPeak }" ::= { sdbMIBNotifications 14 } sdbDevSsHardwareAlertDetected NOTIFICATION-TYPE STATUS current DESCRIPTION "Hardware alert detected. OBJECTS { sdbDevSsHardwareAlert }" ::= { sdbMIBNotifications 15 } sdbMIBCompliance MODULE-COMPLIANCE STATUS current DESCRIPTION "The requirements for conformance to the CONTEG-DATABUS-MIB." MODULE CONTEG-DATABUS-MIB GROUP sdbMIBNotificationGroup DESCRIPTION "The notification group." GROUP sdbMIBDevSensorGroup DESCRIPTION "The sensors group." GROUP sdbMIBDevOutGroup DESCRIPTION "The outlet group." GROUP sdbMIBDevOutMtGroup DESCRIPTION "The outletMetering group." GROUP sdbMIBDevOutSwGroup DESCRIPTION "The outletSwitched group." GROUP sdbMIBDevInGroup DESCRIPTION "The inputMeasures group." GROUP sdbMIBDevStGroup DESCRIPTION "The settings group." GROUP sdbMIBDevSsGroup DESCRIPTION "The systemStatus group." GROUP sdbMIBDevCfGroup DESCRIPTION "The configuration group." GROUP sdbMIBDevIdGroup DESCRIPTION "The identification group." GROUP sdbMIBDevRsGroup DESCRIPTION "resettable attributes in device" GROUP sdbMIBMgmtStatusGroup DESCRIPTION "The databus management status group." GROUP sdbMIBMgmtControlGroup DESCRIPTION "The databus management control group." GROUP sdbMIBDevPerformanceGroup DESCRIPTION "The databus management control group." ::= { sdbMIBCompliances 1 } sdbMIBNotificationGroup NOTIFICATION-GROUP NOTIFICATIONS { sdbDevSsDeviceStatusCodeChanged, sdbDevSsTemperatureAlertDetected, sdbDevSsInputCurrentAlertDetected, sdbDevSsOutletCurrentAlertDetected, sdbDevSsInputVoltageAlertDetected, sdbDevSsOutletCurrentDropAlertDetected, sdbDevSsInputCurrentDropAlertDetected, sdbDevSsSensorChangeAlertDetected, sdbMgmtStsRingStateChanged, sdbDevSsOutletVoltageDropAlertDetected, sdbDevSsBranchCurrentAlertDetected, sdbDevSsBranchVoltageAlertDetected, sdbDevSsNeutralCurrentAlertDetected, sdbDevSsResidualCurrentAlertDetected, sdbDevSsHardwareAlertDetected } STATUS current DESCRIPTION "A collection of notifications." ::= { sdbMIBGroups 1 } sdbMIBDevIdGroup OBJECT-GROUP OBJECTS { sdbDevIdSPDMVersion, sdbDevIdFirmwareVersion, sdbDevIdSalesOrderNumber, sdbDevIdProductId, sdbDevIdSerialNumber, sdbDevIdHardwareAddress, sdbDevIdUnitAddress, sdbDevIdName, sdbDevIdLocation, sdbDevIdVanityTag, sdbDevIdMacAddress, sdbDevIdBuildNumber, sdbDevIdDeviceType, sdbDevIdLocateUnit, sdbDevIdConfigType } STATUS current DESCRIPTION "A collection of objects providing identification information about the device." ::= { sdbMIBGroups 3 } sdbMIBDevCfGroup OBJECT-GROUP OBJECTS { sdbDevCfPhases, sdbDevCfOutletsTotal, sdbDevCfOutletsSwitched, sdbDevCfOutletsMetered, sdbDevCfMaximumLoad, sdbDevCfSensors, sdbDevCfBranches, sdbDevCfNeutral, sdbDevCfTempSensors, sdbDevCfTotals } STATUS current DESCRIPTION "A collection of objects providing configuration information about the device." ::= { sdbMIBGroups 4 } sdbMIBDevSsGroup OBJECT-GROUP OBJECTS { sdbDevSsDeviceStatusCode, sdbDevSsTemperatureAlert, sdbDevSsInputCurrentAlert, sdbDevSsOutletCurrentAlert, sdbDevSsInputVoltageAlert, sdbDevSsOutletCurrentDropAlert, sdbDevSsInputCurrentDropAlert, sdbDevSsSensorChangeAlert, sdbDevSsOutletVoltageDropAlert, sdbDevSsBranchCurrentAlert, sdbDevSsBranchVoltageAlert, sdbDevSsNeutralCurrentAlert, sdbDevSsResidualCurrentAlert, sdbDevSsHardwareAlert } STATUS current DESCRIPTION "A collection of objects providing status information about the device." ::= { sdbMIBGroups 5 } sdbMIBDevRsGroup OBJECT-GROUP OBJECTS { sdbDevRsResetAlerts, sdbDevRsResetPeaksAndDips, sdbDevRsReboot, sdbDevRsZeroInputKWhSubtotal, sdbDevRsZeroOutletKWhSubtotal } STATUS current DESCRIPTION "Groups resettable attributes op the device." ::= { sdbMIBGroups 6 } sdbMIBDevStGroup OBJECT-GROUP OBJECTS { sdbDevStAutoResetAlerts, sdbDevStExtendedNames, sdbDevStPeakDuration, sdbDevStLocalAlertReset, sdbDevStFixedOutletDelay, sdbDevStPowerSaverMode, sdbDevStOutletPowerUpMode, sdbDevStMaximumTemperature, sdbDevStDisplayOrientation, sdbDevStCurrentDropDetection, sdbDevStUsbMode, sdbDevStSensorChangeAlertMode, sdbDevStOutletUnlockOverride } STATUS current DESCRIPTION "A collection of objects providing the actual settings about the device." ::= { sdbMIBGroups 7 } sdbMIBDevInGroup OBJECT-GROUP OBJECTS { sdbDevInKWhTotal, sdbDevInKWhSubtotal, sdbDevInPowerFactor, sdbDevInActualCurrent, sdbDevInPeakCurrent, sdbDevInActualVoltage, sdbDevInMinVoltage, sdbDevInPowerVoltAmpere, sdbDevInPowerWatt, sdbDevInMaxAmps, sdbDevInCTRatio, sdbDevInName, sdbDevInZeroKWhSubtotal } STATUS current DESCRIPTION "A collection of objects providing the actual input measurements of the device." ::= { sdbMIBGroups 8 } sdbMIBDevOutGroup OBJECT-GROUP OBJECTS { sdbDevOutName } STATUS current DESCRIPTION "A collection of objects providing the actual outlet measurements of the device." ::= { sdbMIBGroups 9 } sdbMIBDevOutMtGroup OBJECT-GROUP OBJECTS { sdbDevOutMtKWhTotal, sdbDevOutMtKWhSubtotal, sdbDevOutMtPowerFactor, sdbDevOutMtActualCurrent, sdbDevOutMtPeakCurrent, sdbDevOutMtActualVoltage, sdbDevOutMtMaxAmps, sdbDevOutMtCTRatio, sdbDevOutMtPowerVoltAmpere, sdbDevOutMtPowerWatt } STATUS current DESCRIPTION "A collection of objects providing the actual outlet measurements of the device." ::= { sdbMIBGroups 10 } sdbMIBDevOutSwGroup OBJECT-GROUP OBJECTS { sdbDevOutSwCurrentState, sdbDevOutSwScheduled, sdbDevOutSwUnlock, sdbDevOutSwIndividualOutletDelay, sdbDevOutSwReboot } STATUS current DESCRIPTION "A collection of objects providing the actual outlet measurements of the device." ::= { sdbMIBGroups 11 } sdbMIBDevSensorGroup OBJECT-GROUP OBJECTS { sdbDevSnsType, sdbDevSnsValue, sdbDevSnsName, sdbDevMsIntTemperature, sdbDevMsExtTemperature, sdbDevMsIntTemperaturePeak, sdbDevMsExtTemperaturePeak, sdbDevMsResidualCurrent, sdbDevMsResidualPeak } STATUS current DESCRIPTION "A collection of objects providing the actual environmental measurements of the device." ::= { sdbMIBGroups 12 } sdbMIBMgmtStatusGroup OBJECT-GROUP OBJECTS { sdbMgmtStsDevices, sdbMgmtStsAddressableDevices, sdbMgmtStsNewDevices, sdbMgmtStsDuplicateDevices, sdbMgmtStsRingState, sdbMgmtStsRingBreachIndex } STATUS current DESCRIPTION "A collection of objects providing management status information about the databus." ::= { sdbMIBGroups 13 } sdbMIBMgmtControlGroup OBJECT-GROUP OBJECTS { sdbMgmtCtrlScan, sdbMgmtCtrlRenumberAllFromN, sdbMgmtCtrlRenumberZeros, sdbMgmtCtrlDevUnitAddress, sdbMgmtCtrlDevHardwareAddress, sdbMgmtCtrlDevIsNew, sdbMgmtCtrlDevIsDuplicate } STATUS current DESCRIPTION "A collection of objects providing management control information about the databus." ::= { sdbMIBGroups 14 } sdbMIBDevPerformanceGroup OBJECT-GROUP OBJECTS { sdbDevPerformanceValue, sdbDevPerformanceMax, sdbDevPerformanceLimit, sdbDevPerformanceName, sdbDevPerformanceResetReason, sdbDevResetUptime } STATUS current DESCRIPTION "A collection of objects providing performance information about the MCU" ::= { sdbMIBGroups 15 } END